Magnetic Contactor & Thermal overload CRC Series 100A-800A 4-Pole AC Coil
|
|
Jim D. Gray & Associates, Inc. - Distributing |
|
CAGE NO. 4XGF3 DUNS 178043733 |
|
972-699-9976 |
|
Part No |
ACS Rating @ 440V |
NEMA Starter size |
UL508 (HP) |
EC-60947 (kW,A) |
Endurance ( X 10,000 operations) |
# of Aux.contacts |
OL relay |
||||||||||||
|
4-Pole AC Coil |
Rated Thermal Current (lth) |
Single Phase |
AC motor 3 phase |
AC1 Duty |
AC3 Duty |
||||||||||||||
|
115V |
230V |
200V |
230V |
460V |
575V |
200-240V |
380-440V |
500-550V |
690V |
Electrical |
Mechanical |
NC |
NO |
||||||
|
CRC-100/4 |
100A |
|
160A |
7.5 |
15 |
30 |
30 |
60 |
60 |
150A |
30kW 105A |
55kW 105A |
55kW 85A |
55kW 65A |
100 |
500 |
2 |
2 |
CTK-100 |
|
CRC-125/4 |
125A |
|
160a |
10 |
20 |
40 |
40 |
75 |
75 |
150A |
37kW 125A |
60kW 120A |
60kW 90A |
60kW 70A |
100 |
500 |
2 |
2 |
CTK-100 |
|
CRC-150/4 |
150A |
4 |
210A |
15 |
25 |
40 |
50 |
100 |
100 |
200A |
45kW 150A |
75kW 150A |
90kW 100A |
90kW 100A |
100 |
500 |
2 |
2 |
CTK-150 |
|
CRC-180/4 |
180A |
|
230A |
15 |
30 |
60 |
60 |
125 |
125 |
230A |
35kW 180A |
90kW 180A |
110kW 180A |
110kW 120A |
100 |
500 |
2 |
2 |
CTK-220 |
|
CRC-220/4 |
220A |
|
275A |
15 |
40 |
60 |
75 |
150 |
150 |
260A |
75kW 250A |
132kW 250A |
132kW 200A |
132kW 150A |
100 |
500 |
2 |
2 |
CTK-220 |
|
CRC-300/4 |
300A |
5 |
350A |
|
|
100 |
100 |
200 |
200 |
350A |
90kW 300A |
160kW 300A |
160kW 250A |
200kW 220A |
100 |
500 |
2 |
2 |
CTK-400 |
|
CRC-400/4 |
400A |
2 |
450A |
|
|
125 |
150 |
300 |
300 |
420A |
125kW 400A |
220kW 400A |
225kW 350A |
250kW 300A |
50 |
500 |
2 |
2 |
CTK-400 |
|
CRC-600/4 |
600a |
6 |
660A |
|
|
150 |
200 |
400 |
400 |
660A |
1190kW 630A |
330kW 630A |
330kW 500A |
330kW 420A |
50 |
500 |
2 |
2 |
CTK-600 |
|
CRC-800/4 |
800A |
|
900A |
|
|
200 |
300 |
600 |
600 |
800A |
220kW 800A |
440kW 800A |
500kW 720A |
500kW 630A |
50 |
500 |
2 |
2 |
CTK-600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Type |
Normal |
AC/DC Common Coil |
|
|
Auxuliary contacts & options for CRC 100-800 |
||||||||||||||
|
|
Voltage |
AC 50/60 Hz |
DC |
|
|
Part No. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CRC-100 thru CRC-400 |
24V* |
24-25V |
24V |
|
|
CA-100 |
1 NO, 1 NC side mount |
|
|
|
|
|
|
||||||
|
48V* |
48-50V |
48V |
|
|
AR-100 |
Mechanical interlock for reversing contactor assemblies (CRC-100, CRC-125 & CRC-150) |
|||||||||||||
|
100-200V |
100-240V |
100-220V |
|
|
AR-180 |
Mechanical interlock for reversing contactor assemblies (CRC-180, CRC-220, CRC-300, & CRC-400) |
|||||||||||||
|
300V |
265-347V |
|
|
|
AR-600 |
Mechanical interlock for reversing contactor assemblies (CRC-600 & CRC-800) included base plate |
|||||||||||||
|
400V |
380-450V |
|
|
|
CRC-100R |
Reversing baseplate for CRC-100 |
|||||||||||||
|
500V |
440-575V |
|
|
|
CRC-125R |
Reversing baseplate for CRC-125 |
|||||||||||||
|
CRC-600 thru CRC-800 |
100V |
100-172V |
100-110V |
|
|
CRC-150R |
Reversing baseplate for CRC-150 |
||||||||||||
|
200V |
200-240V |
200-220V |
|
|
CRC-180R |
Reversing baseplate for CRC-180 |
|||||||||||||
|
300V |
265-347V |
|
|
|
CRC-220R |
Reversing baseplate for CRC-220 |
|||||||||||||
|
400V |
280-450V |
|
|
|
CRC-300R |
Reversing baseplate for CRC-300 |
|||||||||||||
|
500V |
440-575V |
|
|
|
CRC-400R |
Reversing baseplate for CRC-400 |
|||||||||||||
|
|
*Available in CRC-100 thru CRC-220 only |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
Thermal Overloads |
|||||||||||||
|
|
|
|
|
|
|
Setting ranges |
|||||||||||||
|
|
|
|
|
|
|
CTK-100 |
34-50, 39-57, 43-65, 54-80, 65-100, 85-125 |
|
|||||||||||
|
|
|
|
|
|
|
CTK-150 |
34-50, 39-57, 43-65, 54-80, 65-100, 85-125, 100-150 |
|
|||||||||||
|
|
|
|
|
|
|
CTK-220 |
65-100, 85-125, 100-160, 120-180, 160-240, |
|
|||||||||||
|
|
|
|
|
|
|
CTK-400 |
85-125, 100-160, 120-180, 160-240, 220-300, 260-400 |
|
|||||||||||
|
|
|
|
|
|
|
CTK-600 |
200-300, 260-400, 400-600, 520-800 |
|
|||||||||||